Interactive Fire Control Panel IFS 7002 is an up-to-date, high reliable, multi-functional and versatile device, providing the user with unexpected potential in the design, installation and operation of addressable fire alarm systems.

Brand: UniPOS
Origin: Bulgaria

TECHNICAL DATA:

Physical configuration:
– 1 fire alarm loops
– 2 monitored outputs
– 1 relay outputs for fire condition
– 1 programmable relay outputs for fire condition
– 1 relay output for fault conditions

Fire alarm zones:
– Maximum number of zones – 64
– Maximum number of fire detectors and in-out devices – 60

Fire alarm loops:
– Maximum number of fire detectors in a loop – 125
– Connecting line – two-wire shielded
– Maximum resistance of a loop – 100
– Output resistance of a loop – 20
– Maximum consumption of a loop – 200mA

Monitored outputs: – 2 pcs
– Type – potential
– Еlectrical characteristics – (24±5)V/0,5A

Relay output for fire conditions – 1 pc
– Type – potential free, switching
– Electrical characteristics – 3A/125VAC; 3A/30VDC

Relay (programmable) output for fire conditions – 1 pc
– Type – potential free, switching
– Electrical characteristics – 3A/125VAC; 3A/30VDC

Relay output for fault conditions – 1 pc
– Type – potential free, switching
– Electrical characteristics – 3A/125VAC; 3A/30VDC

Performance:
– Control over fire alarm loops and monitored outputs for fault conditions (short circuit and interruption) and automatic reset
– Dedicated led indication per fire zone
– Detection of removed devices in the loops and automatic reset
– Ability to set the zones in Coincidence Mode
– Two phases of Fire condition, programmable time for Fire condition stage I, separately for each zone
– Option to prolong the time period for Fire condition stage I with programmable inspection period, specified for each zone
– Built-in sounder for fire condition – one tonal, discontinuous, can be switched off
– Built-in sounder for fault condition – one tonal, discontinuous, can be switched off
– Built-in real time clock
– Set of test modes and options for adjustment

– Setting the clock:
– Checkups on light and sound indications
– Test of fire alarm zones
– Adjustment of outputs and integrated external devices
– Programming of parameters and modes of operation
– Remote programming of the parameters from distant operator control point

– Energy independent event log of registered events with the events type, date and hour – up to 1023 events
– Interfaces for communication with external devices – CAN 2.0B and USB.

Indications of registered events:
– Light indication – LED
– Text messages – LCD display, 320 х 240 points, backlit
– Sound signaling – built-in sounder

Power supply:
Mains:
– voltage – 220/230V
– frequency – 50Hz

Back up batteries:
– battery type – lead, gel electrolyte
– number of batteries – 2 pcs
– connection – serial connection
– nominal voltage of the backup battery – 2x12V DC
– nominal capacity C20 – 7Ah
– charge voltage – 28V

Consumption on back up batteries supply:
– at 24V – <160mA
– at 26V – < 150mA

Power supply to external devices:
– Voltage – (24±5) V
– Maximum current value (including current of monitored outputs) – 1А

Dimensions:
– Overall dimensions – 286 x 148 x 125 mm
– Weight (batteries not included) – 1.240 kg.